Pre-terminated fiber optic cable: types, specs and how to order
What pre-terminated (factory-terminated) fiber optic cable is, the indoor, outdoor and FTTH types, its insertion loss against field termination, and what to state when you order it.
What is pre-terminated fiber optic cable?
Pre-terminated fiber optic cable is cable that arrives with its connectors already fitted, polished and tested. It is also called factory-terminated fiber, pre-connectorized cable or a fiber cable assembly, and in British English pre-terminated fibre. Prysmian describes it as cable “pre-assembled, tested and terminated with a connector”, fully tested end to end before it is delivered. On site, installers pull it in and plug it in. They do not splice it or fit connectors in the field.
It is used where installation time and skilled labour cost more than the cable itself: in data centers, building backbones and the drops of FTTH networks.
Which types of pre-terminated cable are there?
| Type | Ends | Where it is used | Fibers |
|---|---|---|---|
| MPO trunk | MPO at both ends, pinned at both ends in TIA-568.3-E | Data-center backbone between patch panels | 8, 12, 16 or 24 per connector; several connectors per end for higher counts |
| MPO–LC harness | MPO at one end, LC duplex legs at the other | Panel to switch or server | 8 to 24 |
| Breakout (fan-out) trunk | LC or SC on every fiber at both ends, with staggered legs | Riser and backbone links without MPO hardware | Any count the cable holds |
| Pre-connectorized drop | Hardened SC/APC at the terminal end; hardened or standard SC/APC at the home | FTTH drop from a terminal to the home | 1, 2 or 4 |
| Multiport terminal with stub | 4, 6, 8 or 12 hardened ports on a sealed terminal; a factory stub cable joins it to the network | Distribution point that serves the drops | 4–12 ports |
In FTTH the last two types work together. Corning’s multiport terminal, for example, has 4 to 12 hardened single-fiber ports. Its stub cable is either spliced into the network or ordered pre-terminated with a multifiber connector, and each home’s drop then plugs into a port.
Pre-terminated (factory-terminated) or field-terminated: which is better?
| Pre-terminated | Terminated or spliced on site | |
|---|---|---|
| Single-mode connector loss | About 0.1–0.2 dB (factory made); a hardened OptiTap connector is 0.15 dB typical, 0.50 dB maximum | 0.5–1.0 dB for a connector terminated in the field, with a risk of poor reflectance |
| Testing | Every connector tested in the factory, with a report per assembly | Tested after installation; failures mean rework on site |
| Site crew | Pulling and plugging in; fewer engineers and no splicing tools | Splicing or termination crews and equipment at each point |
| Lengths | Fixed at the factory: each route must be measured first | Cut to length on site |
| Waste | Little leftover cable | Drum ends and offcuts to remove |
The loss figures come from the Fiber Optic Association and Corning’s datasheet. TIA-568 allows up to 0.75 dB per mated connection, which the FOA calls generous for anything but MPO connectors.
The choice usually comes down to two questions. Is labour expensive or scarce where you build? Pre-terminated wins. Are the routes still uncertain, or very long? Splice. A common FTTH design does both, as Corning’s terminals show: the feeder and distribution cable are spliced, and the terminals and drops plug in.
Indoor, outdoor and armored pre-terminated cable
The same assembly comes in different jackets, and the route decides which one you need:
| Route | Construction to ask for |
|---|---|
| Inside a building, riser or data center | Indoor cable with the fire rating your code asks for (LSZH, riser or plenum) |
| Between buildings, in ducts | Outdoor or indoor/outdoor cable, water-blocked and UV-resistant, with a pulling eye and sleeve over the connectors |
| Direct burial or where rodents are a risk | Armored outdoor cable; toneable if it has to be located later |
| Poles | Aerial drop or self-supporting cable, with the hardened connectors rated for outdoor use |
Single-mode (OS2, G.652.D or G.657) suits long runs and FTTH; multimode (OM3 or OM4) suits short data-center links. The fiber type is fixed when the assembly is made, like the length.
What to state when you order
| Item | Example | Why it matters |
|---|---|---|
| Fiber type | G.657.A2 for drops; G.652.D for long outdoor runs; OM4 or OS2 in a data center | Bend performance and compatibility with the rest of the link. See G.652.D vs G.657 |
| Fiber count and connector at each end | 12 fibers, MPO-12 female to MPO-12 female; or 1 fiber, hardened SC/APC to SC/APC | The assembly cannot be changed once it is made |
| Polish | APC for PON and FTTH; UPC where the equipment needs it | Reflectance; APC and UPC do not mate |
| Hardened connector system | The system your terminals use | A drop’s hardened connector has to fit the terminal’s ports |
| Length | Measured route plus slack, rounded up to the next standard length | Prysmian’s ezDROP, for example, comes from 50 to 2,000 ft, in 25 ft steps to 200 ft and 50 ft steps above |
| Cable construction | Indoor LSZH, outdoor, armored; flat or round drop; toneable for buried drops | Fire rules, rodents, locating buried cable later |
| Breakout and pulling | Leg length and stagger, pulling eye, protective sleeve | Lets a trunk go through ducts and trays without damage |
| MPO polarity and pinning | Method B, Type-B trunk, pinned both ends | See MPO polarity methods |
| Labels | Both ends, by rack and port or by street address | Saves hours of tracing during installation |
| Test report | Insertion loss per connector; return loss for single-mode; at 1310 and 1550 nm | Proof before shipping, and a baseline for later faults |
| Packing | Boxed or on a reel, labelled per cabinet or per street | Corning ships terminal stubs up to 350 ft in a box and longer ones on a reel |
How to measure lengths without waste
- Walk or survey each route, including rises, drops and detours around obstacles. Plans are rarely accurate enough for a fixed-length cable.
- Add the slack your design rules require at each end, for the terminal or panel and for a future move.
- Round up to the next standard length. A drop that is 5 m too short has to be replaced; one that is 10 m too long is coiled in a slack storage point.
- Group the lengths. A few standard lengths for drops, bought in quantity, cost less and ship sooner than a different length for every home.
How we supply it
ZeroLine Connect supplies pre-terminated cable from audited factories in and around Wuhan’s Optics Valley, each named in our offer:
- MPO trunks, harnesses and cassettes with 8, 12, 16 or 24 fibers per connector, in OS2 and OM3 to OM5, built to your polarity method, tested for insertion loss and labelled to your rack plan.
- Pre-connectorized drops in set lengths with SC/APC or hardened connectors, factory tested.
- Fiber access terminals with 8 or 16 hardened ports, and the splitters, closures and boxes around them.
- Patch cords and pigtails with insertion and return loss measured on every cord.
Send the routes and the table above as part of your bill of materials (see how to send an FTTH BOM), or upload it here. We quote the assemblies with the cable, terminals and splitters, inspect production before it ships and deliver everything in one consignment.
Sources
- Prysmian UK, “What are pre-terminated fibre cables?”, 17 December 2024. prysmian.com
- The Fiber Optic Association, “Calculating Fiber Optic Loss Budgets” (connector and splice loss, TIA-568 maxima). thefoa.org
- Corning, OptiSheath MultiPort Terminal product family specification (ports, stub options, OptiTap and OptiTip loss). corning.com
- Corning, “OptiTap and OptiTip connectors” (hardened connectors for drops). corning.com
- Prysmian North America, ezDROP preconnectorized fiber drop cable datasheet (connectors, lengths, loss). prysmian.com
- AFL, pre-terminated drop cable assemblies (cable types, fiber counts 1, 2 and 4). aflglobal.com
- TIA, “TIA Issues Updated Optical Fiber Cabling Component Standard, ANSI/TIA-568.3-E”, 29 September 2022. tiaonline.org